MCT4 Multi-Loop Touch Screen Controller 1/4 DIN

P Series Panel Mount P91 / P41 and B42 Board Level

Profile Ramp-Soak Control Special Features



P Series Ramp Soak Controllers                      B42 Profile PID Control Board

________________________________________________________

.

Faceplate Recorders Layout, Keypad Operation & Annunciation Description

P Series Ramp Soak Controllers

_________________________________________________

Annunciation & Series Operational Description

P91 front panel

Return to Top of Page

P Series Configuration Options

The P Series allows multiple configuration options for process variable inputs, control outputs, alarms, events, digital input functions, PV/SP Retransmission, transmitter power supply,Security, multiple Profile settings, Serial Modbus RTU communications and more. Below are descriptions of these and other instrument configurations.

Return to Top of Page

P Series Universal Input Details

P Series offers a Universal Signal Input for the following:

Standard

Thermocouple: J, K, T, E, B, R, S, N, L, C, P

RTD: PT 100 DIN, PT100 JIS

Voltage: 0-60 mV

.

Optional (as specified in order matrix - no cost adder)

0-10V, 0-1V, 0-5V, 1-5V

0-20/4-20mA

.

Input Resolution is an industry leading 18 bit

.

Unit Selection: C, F, or PU (process units)

.

Decimal Point Selection

T/C and RTD: no decimal point or one decimal point

Linear Inputs: no decimal point or one, two or three decimal point

.

Return to Top of Page

P Series Control Outputs

Control Output Type Description

  • Control Outputs: Up to 2 isolated PID control outputs; to have two PID outputs #1 must be PID & output #2 is default PID Cool. Available hardware outputs are:
    • relay 2A/240 VAC resistive (SPST)
    • ssr driver - 5VDC/30mA or 14VDC/40mA
    • triac 1A/240VAC
    • 4-20/0-20mA into 500 ohms
    • 1-5/0-5VDC or 1-10/0-10VDC
  • Alarm or Event Outputs: The P41 has up to 3 and the P91 up to 2 configurable alarm or event outputs when Output #2 configured as an alarm or event. When Output #2 is a PID control output the P41 has up to 2 and the P91 has one alarm or event outputs. Available hardware for output #3 and specific to the P41output #4.
    •  relay 2A/240 VAC resistive (SPST except P41 output#3 SPDT)
    • ssr driver - 5VDC/30mA or 14VDC/40mA
    • triac 1A/240VAC
  • Retransmission PV or SP:
    • 0-20/4-20mA or 0-5/1-5VDC is available in lieu of alarm/event output #4 specific to the P41 output #5.
    • Multi-zone programming can be implemented by using SP retransmission to deliver a master setpoint to one, two, three or more client controllers with holdback from any client if PV deviates from SP value by more than a set value per client controller (deviation or deviation band alarm/client wired to event input on P41/91).
  • Transmitter Power Supply [isolated] is available in lieu of alarm/event output #2, # 3 & #4 and specific to the P41, output #5
  • Communications RS232/485 Modbus
    • Communications is available as Output #5

Control Output by Sequence Description

Control Outputs - Up to 4 Control outputs & Communications:

  • Output #1: PID or on-off heat or cool control output (relay, ssr driver, triac or linear mA or VDC)
  • Output #2: PID or on-off cool control output (relay, ssr driver, triac or linear mA or VDC), or Alarm or Event output (relay, ssr driver or triac) or Isolated Transmitter Power Supply
  • Output #3: Alarm or Event output (relay, ssr driver or triac), or Isolated Transmitter Power Supply.
  • Output #4 (P41 only): Alarm or Event output (relay, ssr driver or triac), SP or PV Retransmission (mA or VDC) or Isolated Transmitter Power Supply.
  • Output #5: SP or PV Retransmission (mA or VDC), Isolated Transmitter Power Supply or Modbus RTU RS485 or RS232.

Return to Top of Page

P Series Event Input

Event Input: Dry Contact configurable to Run, Hold, Abort or Jump to next Segment within a profile, Manual Mode, Failure Transfer (pre-configured output status), Off (all outputs off) and selection of PID#2.

Return to Top of Page

P Series Auto-tune and PID #1 and #2

The Auto-tune (A/T)function allows the user to simplify initial setup for a system. A clever algorithm is provided to obtain an optimal set of control parameters (PID) for the process; the A/T can be applied either as the process is warming up (cold start) or as the process has been in a steady state (warm start).

Fuzzy Control is another feature whose function is to adjust PID parameters from time to time in order to make manipulation output value more adaptive to various processes.The intended results are to have the process reach a predetermined setpoint in the shortest time with minimal overshoot or undershoot during the power-up or external load disturbance.

Two Sets of PID Parameters: The operator may configure the P Series offers with up to two sets of PID parameters. The PID parameters may become active either by a Digital Event input (see directly above) or configured per segment within a profile.

Return to Top of Page

P Series Home Page / SEL function

Unique SEL function (Home Page) provides user flexibility & operator ease of use: Parameters most significant to the operator [up to 8] can be configured to display in sequence when the scroll key is depressed.  [P, I, D,  Shift, Cycle 1, deadband, etc., or nothing displayed].

Return to Top of Page

P Series Security / Password

The Password configuration allows user to configure necessary security to insure appropriate operator actions. The Home Page / SEL functions allows for custom security settings - refer to Home Page / SEL configuration.

P91 password

The password value configuration is from 0 to 9999.

Return to Top of Page

_____________________________________________________________________________________

Global Profile Configurations

Below is a description of the Global Settings specific to Profile configuration & operation

Global Profile Configuration - Starting & Ending SP Value

STAR - Setpoint value at start of each profile:Current PV, controller SP1 value or STSP Start SP value (configured within the profile configuration; the STSP value entered under profile configuration is of interest only if it is selected as Global value here).

END - Setpoint value at end of profile: FSP Final SP value for each program, Controller SP value or OFF, all outputs go off except end of profile event relay.

Global Profile Configuration - Delayed Program Start

DLAY - Delay time (HH:MM) between profile initiation & profile start: configurable from 0:00 to 99:59 (hh:mm)

Global Profile Configuration - Power Fail Recovery Logic

PFr - Power Fail Recovery: Continue profile from last SP value, Start to run from current PV, abort profile and control from current SP or Off with all outputs off.

Global Profile Configuration - Holdback Wait Time

HBT - Holdback Wait Time: If configured within a segment the Holdback Wait Time is configurable from 0:00 to 99:59 (hh:mm) or infinite. Details on the Holdback feature are shown below in Profile Configuration - Holdback Band and Segment Configuration - Holdback Type.

Return to Top of Page

___________________________________________________________________________

Profile Configurations

Below is a description of the Settings specific to a Profile; each Profile may have unique settings.

Profile Configuration - Holdback Band (Guaranteed Soak)

The Holdback Band, sometimes known as Guaranteed Soak, may apply to both Ramp & Soak segments with the Band value common to any segment within a specific Profile. Set values may be from 1 to 999F (1 to 555C).

The Holdback Type described below under Segment Configurations configures Holdback as Disabled, Low Deviation, High Deviation or a Band around SP; see Holdback Type below.

The Holdback Wait Time value described above under "Global Profile Configurations" will allow the profile to advance out of Hold (in Hold due to PV being outside the Holdback Band) after the configured time has elapsed. The Holdback Time may be set to infinite so that the Holdback time is not used in the Holdback control logic.

Whenever the PV exceeds the Holdback Band and Holdback Type (deviation high, low or band configured per segment) the profile will be placed in Hold. The profile will stay in Hold until the PV value is within the limits of the Holdback Band and if so globally configured the Holdback Wait Time is set to infinite. If the Holdback Wait Time is set to a time period and the PV value remains outside the Holdback Band the profile will automatically revert to Profile Run mode (no longer in Hold) after the Holdback Wait Time is exceeded.

Profile Configuration - Start Setpoint Value - STSP

Under the Global Profile Configurations the STAR - Starting Setpoint configuration is selected; choices are Current PV, controller SP1 value or STSP Start SP value. When the STSP is selected the value entered in the STSP within the Profile Configuration is used at the start of every Profile.

The Starting Setpoint value entered is where this specific Profile will start its' first Ramp or Dwell segment. The actual value entered may be from anywhere in the configured input range.

Profile Configuration - Time Configuration for Ramp & Dwell

Ramp Rate Configuration: Ramp Rates are configurable in hh:mm, mm:ss from the Start SP OR in units per minute or hour.

Dwell (soak) Time Configuration: Dwell time is configurable hh:nn or mm:ss.

Return to Top of Page

________________________________________________________________________________________________

Segment Configurations

The Segment configuration begins by selecting the segment number which is dependent upon which Profile is being configured.

Profiles 1 - 4 can start / end from segment numbers 0 to 15 (total of 16 segments)

Profiles 5 - 7 can start / end from segment numbers 0 to 31 (total of 32 segments)

Profiles 8 - 9 can start / end from segment numbers 0 to 63 (total of 64 segments)

.

Each Segment can be configured as a Ramp, Dwell, Jump (jump to another segment within the profile) or End.

 

 

Segment Configuration - Target Setpoint for Ramp Segment and Ramp Time Duration

.

Ramp Target Setpoint: If the Segment is configured as a Ramp enter the Target Setpoint value (any value within the input's range)

.

Ramp Time Duration: Configure the Ramp Rate time in the units configured as hh:mm, mm:ss or units per minute or hour as described under

Time Configuration for Ramp & Dwell.

Return to Top of Page

.

.

Segment Configuration - PID #1 & #2 and Event Output Selection

.

PID Set Configuration: Within each Segment the PID #1 and #2 may be selected for use.

Note PID values may also be changed from PID #1 to PID#2 by the digital event input if so configured (an instrument configuration).

.

Event Output Selection: Within each Segment up to 3 relay outputs may be configured to be active (on) during a segment. The number of Event Relays is dependent upon model (P41 has up to 3 relays and P91 up to 2 relays) and hardware ordered; refer to part number matrix below. As these relays may also be configured as alarms there may be fewer than the maximum number allowed.

 

 

Segment Configuration - Holdback Type & Logic Description

.

Holdback Type: Within each Segment the Holdback Type may be configured as OFF, Low Deviation, High Deviation or Band.

When configured for Low Deviation, High Deviation or Band anytime the PV is outside the Holdback Band the profile will be put in Hold until such time the PV is within limits OR the Holdback Wait Time (if so configured) is exceeded.

.

Holdback Review below

The Holdback Band, sometimes known as Guaranteed Soak, may apply to both Ramp & Soak segments with the Band value common to any segment within a specific Profile. Set values may be from 1 to 999F (1 to 555C).

The Holdback Type described above configures Holdback as Disabled, Low Deviation, High Deviation or a Band around SP; see Holdback Type below.

The Holdback Wait Time value described above under "Global Profile Configurations" will allow the profile to advance out of Hold (in Hold due to PV being outside the Holdback Band) after the configured time has elapsed. The Holdback Time may be set to infinite so that the Holdback time is not used in the Holdback control logic.

Whenever the PV exceeds the Holdback Band and Holdback Type (described in this section above) the profile will be placed in Hold. The profile will stay in Hold until the PV value is within the limits of the Holdback Band OR if so globally configured the Holdback Wait Time is set to infinite. If the Holdback Wait Time is set to a time period and the PV value remains outside the Holdback Band the profile will automatically revert to Profile Run mode (no longer in Hold) after the Holdback Wait Time is exceeded.

Return to Top of Page

Segment Configuration - Time Duration for Dwell

Dwell Time Configuration: Configure the Dwell time in the units configured as hh:mm, mm:ss described under Time Configuration for Ramp & Dwell.

 

 

Segment Configuration - Segment Jump and Repeat Cycle

.

Segment Jump: A Target Segment may be entered to "Jump To" within the Profile being configured at the end of the current Segment. The number of segments per profile is shown under the general Segment Configuration above.

.

Repeat Jump Cycle: Enter the number of cycles the Segment Jump should occur; from 1 to 9,999 or infinite.

 

 

Segment Configuration - Final Setpoint for end Segment of Profile

 

Final Setpoint: Enter the final Setpoint for the end or last Segment.

.

__________________________________________________________________________________________________

Return to Top of Page

P Series Order Matrix

P Series order matrix

Return to Top of Page