B Series B41 & B42 PID Board Level Controls
from $165 List
.
Future Design Controls B Series board level controls, models B41 and B42, are based upon the 1/4 DIN panel mount 4100 and P41 controllers. Typically these products are used as sub-panel mount controllers and accessed by a serial modbus master device; i.e. PLC, HMI display, PC, etc.
.
B41 PID Steady State PID Board Level Control
.
The B41 is a steady state board level PID loop control available with an optional Display/Operator Interface Board.
.
The B41 and its Operator Interface Board are typically specified when space prevents a DIN style panel control from being used. The optional display interface board may be mounted in an opening behind a panel overlay with the PID control board mounted remotely to the display and has a secure connection to the main B41 board. The display board has four buttons to change Setpoint and configuration parameters in the same fashion as the panel mount DIN control 100 Series FDC-4100.
.
When used without the optional Display Board all setup & operator interface must be done through the optional Modbus communication port.
.
Click here to view B41 Specification lower on this page.
.
.
B42 PID Profile Ramp Soak PID Board Level Control
.
The B42 is a Profile Ramp Soak board level PID loop control. An optional display board is available but intended only for temporary use, typically for configuration and/or troubleshooting.
.
The B42 is based upon the 1/4 DIN P41 single loop control. The B42, with up to 9 Profiles (up to 64 segments/profile), up to 4 control outputs, configurable Event input, PID Selection by Segment or Event input, PV/SP Retransmission (15-bit), serial Modbus RTU communication, fast scan rate (200ms), make it the right choice for a Profile control.
The B42 offers a full range of universal high resolution (18 bit) inputs; T/C, RTD and linear mA/VDC inputs. Power requirement of either 90-250 VAC or optional 11-26 VAC/VDC allows the B42 to be used virtually anywhere.
Note: The B42 is commonly used as a component in Future Design Controls nCompass LC control system.
Click below to view B42 Profile and Operational Specifications lower on this page.
- B42 Profile Specifications
- B42 Operational Specifications
.
EnVision PC Based SCADA Software for B Series Control Boards
.
EnVision, a FREE PC based SCADA software offers unrivaled flexibility for remote SCADA access to up to a mix of 128devices including loop controls, 8-channel analog input modules and Orion-M iSeries control systems.
- Data Logging: Each of the 128 devices, whether a mix P Series or other Future Design products, can have their data saved to the hard disk at user-defined rates. With up to 129 concurrent data log files, EnVision offers unparalleled data logging flexibility. Data file analysis tools (digital and trend) make looking at schedule run data a simple task
- Profile Management: EnVision allows the user to open, create, edit and save profiles from the PC interface. It also provides the user with the ability to download profiles to the selected P-Series controller.
___________________________________________________
.
B41 Specification Review
- Power Input:
- 90-250VAC, 47-630hz,12VA, 5W maximum
- 11-26VDC / VAC, 12VA, 5W maximum is optional
- Inputs:
- Universal Process Input:
- Thermocouple: Types J, K, T, E, B, R, S, N, L, C & P
- RTD: PT 100 ohm DIN and PT 100 JIS
- Linear: 0-60mV, 1-5VDC, 0-5VDC, 0-10VDC and 0-20/4-20mA input (mA input special hardware order code)
- Input sample rate: 5 scans/second
- Input Resolution: 18 Bit [262,144] click here for 18 Bit descr.
- Control Outputs:
Up to 2 isolated PID control outputs; to have two PID outputs #1 must be PID & output #2 is default PID Cool. Available hardware outputs are:
- relay 2A/240 VAC resistive (SPST)
- ssr driver - 5VDC/30mA or 14VDC/40mA
- triac 1A/240VAC
- 4-20/0-20mA into 500 ohms
- 1-5/0-5VDC or 1-10/0-10VDC
- Transmitter Power Supply [isolated] is available in lieu of control output #2.
- Alarm Outputs:
Up to 2 configurable Alarm outputs, Output #3 is a dedicated alarm output with Output #2 available as an alarm when not used as PID cool..
- relay 2A/240 VAC; Output #2 SPST and Output #3 SPDT
- ssrd driver either 5VDC/30mA or 14VDC/40mA
- triac 1A/240VAC
- Communications:
Serial Modbus RS232 or RS485 are typically used. In lieu of Serial Modbus Retransmission may be specified as VDC/ mA retransmission.
___________________________________________________
.
B42 Profile Feature Specification Review
-
9 Programs with up to 64 Segments per program - see below
- Programs 1 - 4 have up to 16 segments
- Programs 5 - 7 have up to 32 segments
- Programs 8 - 9 have up to 64 segments
-
Universal Process Input:
T/C, RTD or specific Linear mA or VDC
-
Event Input:
Configurable to Run, Hold, Run-Hold, Abort, Jump to next Segment, Select 2nd set of PID parameters, Failure Transfer (pre-configured output status), and Manual Mode.
-
Profile Configurations:
Security-Password, Time Base for Ramp and Soak, Configurable Hold-Back (Guarantee Soak & Ramp), Jump To Segment, Repeat, Start Profile Delay, Power Interruption Recovery and more.
-
Communication Options:
RS232/485 Modbus & Retransmission. Click here for Communication_Quick_Guide for use with 3rd party software.
-
Control Outputs - Up to 4 Control outputs & Communications:
-
Output #1: PID or on-off heat or cool control output (relay, ssr driver, triac or linear mA or VDC)
- Output #2: PID or on-off cool control output (relay, ssr driver, triac or linear mA or VDC), or Alarm or Event output (relay, ssr driver or triac) or an Isolated Transmitter Power Supply.
-
Output #3: Alarm or Event output (relay, ssr driver or triac), or Isolated Transmitter Power Supply.
-
Output #4 (P41 only): Alarm or Event output (relay, ssr driver or triac), SP or PV Retransmission (mA or VDC) or Isolated Transmitter Power Supply.
-
Output #5: SP or PV Retransmission (mA or VDC), Isolated Transmitter Power Supply or Modbus RTU RS485 or RS232.
- Program Control Configuration Options
- Up to 9 Programs with up to 64 segments (see above)
- Global Program Settings:
- Starting & Ending Setpoint Values for Program
- Delayed Program Start time in hh:mm
- Power Fail / Recovery logic: Continue from last SP, Continue from current PV, Static Mode SP1, Static mode Start SP (see above) and OFF.
- Holdback Wait Time (Guaranteed Soak/Ramp maximum hold time before program continue).
- Configurable per Segment
- Target SP for Ramp segment and Start SP/Final SP values for segment configured as ramp in units/minute or hour.
- Final SP for end segment
- Event Outputs (up to 3 for P41 and 2 for P91) and selection of PID set #1 or #2.
- Time unit & duration for ramp & dwell: hh.mm, mm.ss and for ramp configurable units/minute or units/hour (0.0 to 900.0F/minute or hour)
- Holdback band and control action: Off, Low deviation, High deviation or Deviation band. (Holdback is also known as Guaranteed Soak / Ramp.)
- Segment Jump and number or Repeat Cycles.
___________________________________________________
B42 Technical Specifications
- Power Input:
- 90-250VAC, 47-630hz,12VA, 5W maximum
- 11-26VDC / VAC, 12VA, 5W maximum is optional
- Inputs:
Universal Process Input:
- Thermocouple: Types J, K, T, E, B, R, S, N, L, C & P
- RTD: PT 100 ohm DIN and PT 100 JIS
- Linear: 0-60mV, 1-5VDC, 0-5VDC, 0-10VDC and 0-20/4-20mA input (mA input special hardware order code)
- Event Input: Dry Contact configurable to Run, Hold, Abort, Jump to next Segment within a profile, Manual Mode, Failure Transfer (pre-configured output status), Off (all outputs off) and selection of PID#2.
- Input sample rate:
- Input Resolution:
- Control Outputs:
Up to 2 isolated PID control outputs; to have two PID outputs #1 must be PID & output #2 is default PID Cool. Available hardware outputs are:
- relay 2A/240 VAC resistive (SPST)
- ssr driver - 5VDC/30mA or 14VDC/40mA
- triac 1A/240VAC
- 4-20/0-20mA into 500 ohms
- 1-5/0-5VDC or 1-10/0-10VDC
- Alarm or Event Outputs:
The P41 has up to 3 and the P91 up to 2 configurable alarm or event outputs when Output #2 configured as an alarm or event. When Output #2 is a PID control output the P41 has up to 2 and the P91 has one alarm or event outputs. Available hardware for output #3 and specific to the P41output #4.
- relay 2A/240 VAC resistive (SPST except P41 output#3 SPDT)
- ssr driver - 5VDC/30mA or 14VDC/40mA
- triac 1A/240VAC
- Retransmission PV or SP:
- 0-20/4-20mA or 0-5/1-5VDC is available in lieu of alarm/event output #4 specific to the P41 output #5.
- Multi-zone programming can be implemented by using SP retransmission to deliver a master setpoint to one, two, three or more client slave controllers with holdback from any client if PV deviates from SP value by more than a set value per slave controller (deviation or deviation band alarm/slave control wired to event input on P41/91 configured to hold the profile).
- Transmitter Power Supply [isolated]
Optional in lieu of control or alarm/event outputs; #2, # 3 & #4 and specific to the P41, output #5
- Communications RS232/485 Modbus
- Security:
Software configurable
- None: All parameters are unlocked
- Password (0-9999) configurable
- Without password no parameters may be changed.
- With password all parameters are changeable
- With password only Home Page (SEL) may be changed.
- Set: Setup Configuration Data is locked
- User: All data locked except SP#1 and alarms #1, #2 and #3. [total 4 outputs]
- All: All data locked