300 Series Standard Special Features

Return to 300 Series.htm


300 Series Controls standard 3 Inputs

Top of Page


High Accuracy 18-Bit A/D and 15 D/A Analog Input & Output

The C, 100, 300 & P Series Controls provide the highest A/D and D/A Analog Input & Output Resolution in the control industry.

Input Resolution is an important specification to a process control's performance & accuracy. FDC's 18 Bit A/D and 15 Bit D/A is the highest Input & Output resolution in the industry. Couple this to our 200 ms input scan and proprietary Fuzzy PID auto-tuning results in a high performance control with the industries lowest pricing.

Click here for more information on Input & Output Resolution.htm

Top of Page


UL Approval Nema 4X 9300 1/16 DIN Control

The 300 Series Controls are UL Approved under Category QUYX2 Process Control Equipment, Component. The file also includes the 9300 1/16 DIN as Nema 4X suitable to be mounted on a vertical position on a flat surface of Type 4X enclosures. Further information may be found at UL Approval.pdf

Top of Page


Display Configuration for Input #1 and Input #2

The Process Variable in the 300 Series Controls [300 Series has two analog & one event input] is configurable as one of the following:

The default display will show the Process Variable as configured above.

The Display Mode for the 300 Series also allows operator viewing of the following:

Top of Page


Remote Setpoint

The 300 Series control platform has 3 inputs, two of which may be configured to accept a Remote Setpoint input:

Remote Setpoint Input: Input #1 and #2 can be configured to accept linear mA/VDC input as the PV or as a Remote Setpoint. When configured as a Remote Setpoint the other input is the PV input.

The Event input [input #3] may be configured to switch between local & remote setpoint. Example Application - Multizone Oven: One 300 Series control [master] retransmits its' setpoint to other 300 Series controls [slaves] insuring each zone control has the same setpoint.

Note: When the SP ramp function is used, the lower display will show the current ramping value. However it will revert to show the set point value whether it is manual enter SP or Remote SP as soon as the up or down key is touched for adjustment. The ramping value is initiated to process value either power up or RAMP and /or set point are changed. Setting RAMP to zero means no ramp function at all.

Top of Page


2nd Set Point & PID variables via Event Input

A 2nd Setpoint and/or PID variables may be selected using the event input available in the 300 Series Controls.  With the event input configured to change SP, PID or SP & PID, a dry contact signal applied to the event input terminals will drive the appropriate change.

The contact closure may come from external device or from an alarm input from the 300 Series Control. Examples with input coming from 300 Series Control:

PID control multiple PID setsTop of Page


Sensor Break Alarm

  • Bumpless Transfer of Proportional Outputs
  • Configurable Proportional Output to a default value 0 - 100%

Bumpless Transfer with Sensor or other control Failure: [applicable to C, 100, 300 & P Series]Upon Sensor or other control Failure the Proportional Outputs can be configured to provide a Bumpless Transfer of the current proportional output.PID bumpless transfer disabledPID with bumpless transferWith the Bumpless Transfer configured and the process load does not change the process can continue to be controlled temporarily as if the sensor is normal. However, once the load changes the process may run away. Therefore you should not rely on bumpless transfer for any extended period of time. For fail safe reason an additional alarm should be used to annunciate a system or sensor failure. Control Outputs configured to a default output 0 - 100%: [applicable to C, 90, 200, 200, 300 & P Series Controls] Upon Sensor or other control Failure the Proportional Outputs can be configured to default a configurable percent output ranging from 0% to 100%. Output #1 when set as an on-off control can be configured to be open or closed.

Note: Outputs configured as alarms are configurable to open or close on control failure. This feature is described in Alarm Logic page.

Top of Page


Dwell Alarm - Reset via Power-up sequence or event input

Dwell Timer Alarm: [applicable to C, 90, 100, 200, 300 & P Series Controls]

One alarm may be configured as a dwell timer alarm. Once configured the dwell time is measured in minutes - the maximum number of minutes vary by control series with the longest being the 300 Series at 6,553 minutes.  Once the process reaches setpoint the dwell timers starts to count down from zero until time out. The dwell timer alarm relay will remain unchanged until time out.  The dwell timer is reset by power up sequence or the  event input may be configured to reset the dwell timer] 

Dwell timer alarm

Top of Page


2 Setpoint Ramp/One Soak Feature

 

Setpoint Ramp / Soak with Dwell Timer: [applicable to C, 90, 100, 200, & 300 Series Controls]When controls are configured for Setpoint Ramp and an alarm as Dwell Timer a one Setpoint Ramp & Soak feature is available. When the control is powered the SP will ramp from existing PV at the configured rate to the control SP. Once SP is achieved the dwell timer will start its' countdown. When the dwell time is achieved the alarm relay will activate and if so wired to shut the system down or alert operator dwell (Soak) time is completed.Two Setpoint Ramps with one Dwell Time: [applicable to 300 Series only] Click here for more information on the Series 300 Special Features.The 300 Series controls with event input configured to change SP offers ability to have a 2nd SP Ramp. PID variables may also be changed when switching to SP2. See above Selection of 2nd Setpoint and/or PID Variables.

PID 2 setpoint one timer function

Above shows 300 Series using Dwell Timer alarm to switch to 2nd SP

Top of Page


Cascade & Differential Control Applications

Differential Control: In certain applications it is desirable to control a second process such that its process value always deviates from the first process with a constant value.

Differential PID Control

 The 300 Series allows the Control & Display to be configured independently as PV #1, PV #2,  PV1-PV2 or PV2-PVI.  For Differential Control Configure the appropriate PV's as PV1 & PV2, configure control as either PV1-PV2 or PV2-PV1 and the control output will function to maintain set differential between the two. The PV display is configured separately from the control and can be set at PV1, PV2, PV1-PV2 or PV2-PV1. Cascade Control- The output of control #1 becomes control #2 SP. Cascade Control requires two controls.

Control #1 has retransmission option configured as to retransmit output #1 % Output. Control #2 accepts Control #1 retransmitted output as its' Remote Setpoint.

Top of Page


View CJC Temperature ValuesCold Junction Compensation [CJC] Temperature Value:

The CJC is used with thermocouple [t/c] inputs to measure the ambient temperature where the t/c's connect to the control and may be viewed at any time. The CJC value is not used by the control when configured for RTD or Linear mA/VDC inputs but may still be viewed. As the CJC value represents the temperature at the control's terminal block [slightly higher than ambient due to heat generated by controller operation] the CJC value may be of interest if the temperature of the panel box the control is mounted is of interest.Via RS485/232 Modbus - Read Historical Minimum & Maximum PV Values and CJC Temperatures: [applicable to C, L, 100, 300 & P Series Controls.The subject values have Modbus addresses and can be read via RS232/485 communications.

Top of Page

Return to:

Process & Temperature Control Page.htm

90 Series.htm

300 Series.htm

100/C Series.htm

B Series.htm (board level control)

Limit Controls.htm

P Series Profile Controls.htm

Future Design Controls: 888.751.5444  csr@futuredesigncontrols.com